STUDY OF THE PERFORMANCE OF AIR CONDITIONING SYSTEM INCORPORATING CHILLED WATER STORAGE | ||||
JES. Journal of Engineering Sciences | ||||
Article 7, Volume 39, No 6, November and December 2011, Page 1343-1360 PDF (229.57 K) | ||||
Document Type: Research Paper | ||||
DOI: 10.21608/jesaun.2011.129445 | ||||
View on SCiNiTO | ||||
Authors | ||||
A.S. Ali1; I.M. Ismail2; M.S. Ahmed3 | ||||
1Grad. Student, Mech. Engineering Dept., Faculty of Engineering, Assiut University, Assiut, Egypt | ||||
2Professor, Mech. Engineering Dept., Faculty of Engineering, Assiut University, Assiut, Egypt. | ||||
3Ph.D., Mech. Engineering Dept., Faculty of Industrial Edu., Sohag University, Sohag, Egypt. | ||||
Abstract | ||||
In the present study, an air conditioning system with a storage tank was constructed and tested. Along the 24 hrs, eight tank-charge cycles were performed to evaluate the effect of variation local ambient temperature on the system performance. A significant variation in the values of COP due to variation in local ambient temperature in Sohag city was recorded. There are two modes of chilled water storage, full-storage and partialstorage. This study deals with partial-storage mode. In this study, a comparison has been carried out between air conditioning system without chilled water storage and that with storage. Configuration of storage tank has a significant effect on system performance. Two storage tanks with aspect ratio of 1.1 and 2.2 were tested. A COP of 1.63 was achieved for the adopted system for no-storage mode. In partial-storage mode, the COP achieved was 1.73 in case of storage tank with aspect ratio 1.1, and 1.79 with aspect ratio 2.2. | ||||
Statistics Article View: 77 PDF Download: 309 |
||||