ASSESSMENT OF AIR DIFFUSION PERFORMANCE INDEX IN A SURGICAL OPERATING ROOM BY COMPUTATIONAL FLUID DYNAMICS TECHNIQUE | ||||
The International Conference on Applied Mechanics and Mechanical Engineering | ||||
Article 41, Volume 18, 18th International Conference on Applied Mechanics and Mechanical Engineering., April 2018, Page 1-15 PDF (1.42 MB) | ||||
Document Type: Original Article | ||||
DOI: 10.21608/amme.2018.34981 | ||||
View on SCiNiTO | ||||
Authors | ||||
A. M. Alabasiry1; E. Elgendy2; K. Elsayed3; M. Fatouh4 | ||||
1Post graduate student, Mechanical Power Engineering Department, Faculty of Engineering, Helwan University, Cairo, Egypt. | ||||
2Associate professor, Mechanical Power Engineering Department, Faculty of Engineering, Helwan University, Cairo, Egypt. | ||||
3Assistant professor, Mechanical Power Engineering Department, Faculty of Engineering, Helwan University, Cairo, Egypt. | ||||
4Professor, Mechanical Power Engineering Department, Faculty of Engineering, Helwan University, Cairo, Egypt. Dean of Faculty. | ||||
Abstract | ||||
ABSTRACT Surgical operating room needs an efficient ventilation system to achieve thermal comfort and clean environment. This paper aims to improve the air distribution in the operating rooms with two operating tables configuration. Six test cases with different numbers, sizes and locations of exhaust air grills have been simulated using CFD and validated with experimental measurements. The air diffusion performance index (ADPI) value has been estimated for each case. The results show that the case with eight exhaust air grills distributed in the four corners of the operating room gives the highest ADPI (63.06%). | ||||
Keywords | ||||
operating room; Air Diffusion Performance Index (ADPI); computational fluid dynamics (CFD); Effective Draft Temperature | ||||
Statistics Article View: 208 PDF Download: 553 |
||||