AN IMPROVED FORMULATION FOR OPTIMAL OVERCURRENT RELAY COORDINATION USING LINEAR PROGRAMMING TECHNIQUE | ||||
The International Conference on Electrical Engineering | ||||
Article 43, Volume 2, 2nd International Conference on Electrical Engineering ICEENG 1999, November 1999, Page 411-423 PDF (2.99 MB) | ||||
Document Type: Original Article | ||||
DOI: 10.21608/iceeng.1999.62531 | ||||
View on SCiNiTO | ||||
Authors | ||||
Ammar A. Hajjar1; A. Y. Abdelaziz2; H. E.A. Talaat3; A. I. Nosseir4 | ||||
1Graduate student, Faculty of Mechanical and Electrical Engineering, Tishreen University, Latakia, Syria | ||||
2Assistant professor, Electrical power & Machines Department, Faculty of Engineering, Ain Shams University, Cairo, Egypt | ||||
3Associate professor, Electircal power & Machines Department, Faculty of Engineering, AM Shams University, Cairo, Egypt | ||||
4Professor, Electrical power & Machines Department, Faculty of Engineering, Ain Shams University, Cairo, Egypt | ||||
Abstract | ||||
In this paper the problem of directional overcurrent relays coordination in interconnected power networks is presented and solved using the optimization theory. Linear programming with Simplex two-phase method is applied to minimize the operating time of the relays. The insignificance of weighting factors and far-end fault consideration in the problem formulation is proved, through a mathematical example, by simulation, mathematically, graphically and by sensitivity analysis. The current transformer (CT) selection is achieved based on the maximum load and fault currents in order to prevent the miscoordination problem resulting from CT's saturation. A complete algorithm for calculating the optimal operating times is introduced and applied to sample examples. | ||||
Keywords | ||||
interconnected networks; overcurrent relay; coordination; Optimization; and enhanced formulation | ||||